3.7.4.16 — Privacy

Copied!
(1) If a room contains not more than 1 water closet, the doorway to the room shall be provided with a full height door that is capable of being locked from the inside.
(2) Except in a room for private use, water closets, urinals, lavatories, showers and bathtubs shall not be visible from the entrance to the room where it contains at least,
(a) two water closets,
(b) one water closet and one urinal,
(c) one shower stall, or
(d) one bathtub.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.