Div. B › Part 3 › 3.4 › 3.4.1

3.4.1.5 — Exterior Exit Passageways

Copied!
(1) Access to an exterior exit passageway from a floor area shall be through exit doors at the floor level.
(2) Every exterior exit passageway that has a drop of more than 500 mm on any side shall have guards on the open sides not less than 1 070 mm high.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.