Div. B › Part 3 › 3.2 › 3.2.1 — General

3.2.1.4 — Floor Assembly over Basement

Copied!
(1) Except as permitted by Sentence 3.2.2.42. (3), 3.2.2.43. (3), 3.2.2.44. (3), 3.2.2.45. (3), 3.2.2.46. (3), 3.2.2.47. (3) or 3.2.2.48. (3), a floor assembly immediately above a basement shall be constructed as a fire separation having a fire-resistance rating conforming to the requirements of Articles 3.2.2.20. to 3.2.2.83. for a floor assembly, but not less than 45 min.
(2) All loadbearing walls, columns and arches supporting a floor assembly immediately above a basement shall have a fire-resistance rating not less than that required by Sentence (1) for the floor assembly.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.