Div. B › Part 3 › 3.4 › 3.4.4 — Fire Separation of Exits

3.4.4.3 — Exterior Passageway Exceptions

Copied!
(1) The requirements of Sentences 3.4.4.1. (1) and 3.2.3.13. (1) and (3) do not apply to an exterior exit passageway provided,
(a) not less than 50% of the exterior side is open to the outdoors, and
(b) an exit stair is provided at each end of the passageway.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.