(1) Except as permitted by Sentences (2) to (4) and (6), every floor area intended for occupancy shall be served by at least two exits.
(2) A floor area in a building not more than 2 storeys in building height, is permitted to be served by one exit provided the total occupant load served by the exit is not more than 60 and,
(a) in a floor area that is not sprinklered, the floor area and the travel distance are not more than the values in Table 3.4.2.1.A., or
(b) in a floor area that is sprinklered,
(i) the travel distance is not more than 25 m, and
(ii) the floor area is not more than the value in Table 3.4.2.1.B.
(3) Except as permitted by Sentence (4), if Sentence (2) permits a single exit from a floor area classified as Group B or Group C occupancy, the exit shall be an exterior doorway not more than 1.5 m above adjacent ground level.
(4) The requirements of Sentences (1) and (2) are permitted to be waived for dwelling units having access to exit conforming to Sentences 3.3.4.4. (1) to (4) and (8).
(5) Exits are not required directly from rooftop enclosures that are provided with access to exits in conformance with Sentences 3.3.1.3. (5) and (6).
(6) Every room containing an assembly occupancy serving a hotel, and located in the building containing the hotel, shall be provided with no fewer than,
(a) three separate egress doorways from the room where the occupant load is more than 600 persons, and
(b) four separate egress doorways from the room where the occupant load is more than 1 000 persons.
(7) Each egress doorway in Sentence (6) shall be considered as contributing not more than,
(a) one-third of the required width where three egress doorways are required, and
(b) one-fourth of the required width where four egress doorways are required.