Div. B › Part 3 › 3.16A › 3.16A.2

3.16A.2.8 — Structural Provisions

Copied!
(1) Except as provided in Sentences (2) and (4), demountable stages and demountable support structures and their structural members shall be designed, erected, assembled and installed,
(a) in conformance with Part 4, or
(b) to conform to good engineering practice appropriate to the circumstances such as that described in ANSI E1.21, “Entertainment Technology - Temporary Structures Used for Technical Production of Outdoor Entertainment Events”.
(2) The reference velocity pressure shall be the appropriate value determined in conformance with Subsection 1.1.2. based on a probability of being exceeded in any one year of 1-in-10 with a 2.5 gust factor.
(3) For purposes of Clause (1) (a), demountable stages and demountable support structures shall be assigned a Normal Importance Category as described in Table 4.1.2.1.B.
(4) Footings shall be designed in accordance with Clause 9.4.4.1.
Tables & Figures referenced
Table 4.1.2.1.B : Importance Categories for Buildings : Forming Part of Sentence 4.1.2.1.(3)
Loading Table 4.1.2.1.B…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.