Div. B › Part 3 › 3.7 › 3.7.4 — Plumbing Facilities

3.7.4.8 — Plumbing Fixtures for Mercantile Occupancies

Copied!
(1) Except as provided in this Article, the number of water closets required for employees in mercantile occupancies shall conform to Table 3.7.4.8.
(2) Except as provided in Sentence (4), the number of water closets required for the public in mercantile occupancies shall be at least one fixture for each 300 males and one fixture for each 150 females, except that,
(a) water closets provided for employees are permitted to be counted as part of those required for the public when these water closets are made accessible to the public, and
(b) where the total area of the mercantile occupancy, excluding basements, is not more than 600 m2, not more than one water closet for each sex need be provided.
(3) Not more than one water closet to serve both sexes need be provided in a Group E occupancy where,
(a) the occupant load is not more than nine persons, or
(b) where the total area of the occupancy, excluding basements, is not more than 300 m2.
(4) For a restaurant classified as mercantile occupancy, the number of water closets and lavatories required shall conform to Article 3.7.4.3.
Tables & Figures referenced
Table 3.7.4.8 : Water Closets for Mercantile Occupancies : Forming Part of Sentence 3.7.4.8.(1)
Loading Table 3.7.4.8…
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.