Div. B › Part 3 › 3.2 › 3.2.8 — Mezzanines and Openings through Floor Assemblies

3.2.8.7 — Sprinklers

Copied!
(1) In a building containing an interconnected floor space, storeys that are wholly or partially within an interconnected floor space and all storeys below an interconnected floor space shall be sprinklered.
(2) In a building containing an interconnected floor space,
(a) waterflow alarm signals from sprinkler systems shall be transmitted to the fire department in conformance with Sentence 3.2.4.8. (4), and
(b) sprinkler systems shall be electrically supervised as required by Sentence 3.2.4.10. (3).
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.