Div. B › Part 3 › 3.2 › 3.2.2 — Building Size and Construction Relative to Occupancy

3.2.2.14 — Rooftop Enclosures

Copied!
(1) A rooftop enclosure for elevator machinery or for a service room shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.83.
(2) A rooftop enclosure for elevator machinery or for a service room, not more than 1 storey high, is not required to have a fire-resistance rating.
(3) A rooftop enclosure for a stairway shall be constructed in accordance with the type of construction required by Articles 3.2.2.20. to 3.2.2.83.
(4) A rooftop enclosure for a stairway need not have a fire-resistance rating nor be constructed as a fire separation.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.