Div. B › Part 3 › 3.2 › 3.2.8 — Mezzanines and Openings through Floor Assemblies

3.2.8.8 — Fire Alarm and Detection System

Copied!
(1) A building containing an interconnected floor space shall be provided with,
(a) a fire alarm system and electrically supervised annunciator conforming to Subsection 3.2.4.,
(b) a system of smoke detectors located,
(i) on the ceiling of each storey in the vicinity of the openings through floor assemblies described in Article 3.2.8.3., except within dwelling units, heat detectors may be installed instead of smoke detectors, and
(ii) as required for the activation of the smoke control system described in Sentences 3.2.8.9. (3), (4), (6) and (7), and
(c) facilities for transmitting a signal to the fire department in conformance with Article 3.2.4.8.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.