Div. B › Part 3 › 3.2 › 3.2.6 — Additional Requirements for High Buildings

3.2.6.8 — Voice Communication System

Copied!
(1) A voice communication system conforming to Article 3.2.4.23. shall be provided in a building if,
(a) the floor of the top storey is more than 36 m above grade,
(b) a floor area or part of a floor area located above the third storey is designed or intended for use as a Group B, Division 2 or 3 occupancy, or
(c) a floor area or part of a floor area located more than 18 m above grade is designed or intended for use as a retirement home regulated under the Retirement Homes Act, 2010 that is a Group C occupancy.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.