Div. B › Part 3 › 3.2 › 3.2.4 — Fire Alarm and Detection Systems

3.2.4.7 — Silencing of Alarm Signals

Copied!
(1) Except as permitted by Sentence (3), a fire alarm system shall be designed so that when an alarm signal is actuated it cannot be silenced automatically before a period of time has elapsed that is not less than,
(a) 5 min for a building not required to be equipped with an annunciator, and
(b) 20 min for any other building.
(2) Except as permitted by Sentences 3.2.4.20. (9) and 3.2.4.23. (2) and (3), a fire alarm system shall not incorporate manual silencing switches other than those installed inside the fire alarm control unit.
(3) Except as provided by Clause 3.2.4.23. (3) (a), in a care and treatment occupancy an alert signal is permitted to be silenced automatically after 1 min.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.