(1) Except as provided in Sentences (4) to (8), a standpipe system shall be installed in every building that,
(a) is more than 3 storeys in building height,
(b) is more than 14 m high measured between grade and the ceiling of the top storey, or
(c) is not more than 14 m high measured between grade and the ceiling of the top storey but has a building area exceeding the area shown in Table 3.2.9.1. for the applicable building height if the building is not sprinklered.
(2) A standpipe system shall be installed in every basement of a building that requires a standpipe system above grade.
(3) A standpipe system shall be installed in every basement of a building that is regulated by Sentence 3.2.2.15. (2).
(4) A standpipe system is not required to be installed in the lowest storey in a building if this storey is a service room that has an area not more than 50 m2.
(5) A standpipe system is not required to be installed in a rooftop enclosure if this enclosure has an area not more than 50 m2.
(6) A standpipe system is not required to be installed in a storage garage conforming to Article 3.2.2.83. provided the building is not more than 15 m high.
(7) A standpipe system is not required to be installed in a dwelling unit that,
(a) extends not more than 3 storeys above grade,
(b) is completely cut off from the remainder of the building so that there is no access to the remainder of the building, and
(c) has direct access to its interior by means of an exterior doorway located not more than 1 500 mm above or below adjacent finished ground level.
(8) A standpipe system is not required to be installed in a building classified as Group C major occupancy,
(a) that is not more than 4 storeys above grade,
(b) that does not contain a public corridor or other common areas,
(c) where each dwelling unit,
(i) is completely cut off from the remainder of the building so that there is no access to the remainder of the building,
(ii) has direct access to its interior by means of an exterior doorway located not more than 1 500 mm above or below adjacent finished ground level, and
(d) that conforms to the requirements of Article 3.2.2.44. or Article 3.2.2.45.