Div. B › Part 3 › 3.1 › 3.1.7 — Fire-Resistance Ratings

3.1.7.5 — Rating of Supporting Construction

Copied!
(1) Except as permitted by Sentence (2) and by Articles 3.2.2.20. to 3.2.2.83. for mixed types of construction, all loadbearing walls, columns and arches in the storey immediately below a floor or roof assembly required to have a fire-resistance rating shall have a fire-resistance rating not less than that required for the supported floor or roof assembly.
(2) Loadbearing walls, columns and arches supporting a service room or service space need not conform to Sentence (1).
(3) Except as provided in Sentence (4) and for noncombustible roof assemblies required by Subclauses 3.2.2.43A.
(4) Except for parts of a building constructed in accordance with Article 3.2.2.7. that are required to be of noncombustible construction, assemblies of noncombustible construction in buildings or parts of buildings permitted to be of encapsulated mass timber construction are permitted to be supported by encapsulated mass timber construction.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.