Div. B › Part 3 › 3.1 › 3.1.6 — Encapsulated Mass Timber Construction

3.1.6.10 — Combustible Components in Exterior Walls

Copied!
(1) Except as provided in Sentence (2), combustible components, other than those permitted by Article 3.1.6.9., are permitted to be used in an exterior wall assembly of a building or part of a building permitted to be of encapsulated mass timber construction provided the wall assembly meets the requirements of Clause 3.1.6.9. (2) (d).
(2) An exterior wall assembly constructed in conformance with Section 6 in MMAH Supplementary Standard SB-2, “Fire Performance Ratings” is deemed to satisfy the criteria of Sentence (1).
(3) Non-loadbearing wood elements permitted in Article 3.1.5.5. need not conform to Article 3.1.6.3. in a building or part of a building permitted to be of encapsulated mass timber construction.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.