Div. B › Part 3 › 3.2 › 3.2.2 — Building Size and Construction Relative to Occupancy

3.2.2.19 — Buildings Containing Impeded Egress Zones

Copied!
(1) A building containing an impeded egress zone and conforming to the appropriate requirements of Articles 3.2.2.20. to 3.2.2.83. is not required to conform to the requirements of Articles 3.2.2.36. and 3.2.2.37. for a Group B, Division 1 major occupancy provided,
(a) the building is sprinklered,
(b) it is not more than 1 storey in building height,
(c) it does not include,
(i) a contained use area,
(ii) sleeping accommodation,
(iii) a high hazard industrial occupancy, or
(iv) a mercantile occupancy,
(d) the building area is not more than 6 400 m2 if the building includes a medium hazard industrial occupancy,
(e) the impeded egress zone does not extend beyond the boundaries of the fire compartment in which it is located, and
(f) the occupant load of the impeded egress zone is not more than 100.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.