(1) The minimum dimensions stated in Table 3.1.6.3. need not apply at cutouts in vertical or horizontal structural mass timber elements where outlet boxes are installed in accordance with Article 3.1.9.3A.
(2) The exposed surfaces of the cutouts described in Sentence (1) need not be protected in accordance with Sentence 3.1.6.4. (1).
(3) Outlet boxes on opposite sides of a structural mass timber element having a fire-resistances rating shall be separated by a distance of not less than 600 mm.