Div. B › Part 3 › 3.2 › 3.2.2 — Building Size and Construction Relative to Occupancy

3.2.2.73 — Group F, Division 3, Any Height, Any Area

Copied!
(1) Except as permitted by Articles 3.2.2.74. to 3.2.2.83., a building classified as Group F, Division 3 shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7. (1), the building shall be sprinklered if it is regulated by Subsection 3.2.6.,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h, except that floor assemblies are permitted to be fire separations with a fire-resistance rating not less than 1 h in a storage garage with all storeys constructed as open-air storeys,
(c) mezzanines shall have a fire-resistance rating not less 1 h,
(d) if the building is not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and
(e) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
Disclaimer. This site provides general access to Ontario Building Code information for reference only. It is not an official source and may omit or summarize content. Always verify requirements with the current OBC and your Authority Having Jurisdiction (AHJ). The Ontario Building Code is Crown copyright © King’s Printer for Ontario. Terms of Use.